Refrigerant dryers


Refrigerant dryers remove water content from compressed air to reach the required dew point. Relative air humidity, which amounts to 100% before drying, decreases only to 21% (0.75g H2O) after the refrigerant dryer (for dew point +30C).

Compressed air that flows into the dryer has a temperature of +300C ÷ +450C and is initially cooled, in air/air pre-cooler, down to +140C ÷ +230C. Subsequently, compressed air is cooled down in the main cooler to the required +30C dew point.

Refrigerant dryers OP series

TypeAir flowConnectionNominal power
kW
Dimensions
(L x W x H)
mm
Weight
kg
m3/hm3/min
OP 05360,6G 3/40,16350 x 497 x 45019
OP 10510,9G 3/40,18350 x 497 x 45020
OP 20721,2G 3/40,22350 x 497 x 45025
OP 301101,8G 3/40,29350 x 497 x 45027
OP 401412,4G 10,61370 x 500 x 76444
OP 501803,0G 10,67370 x 500 x 76444
OP 602163,6G 1 1/40,79460 x 560 x 78953
OP 652464,1G 1 1/40,87460 x 560 x 78960
OP 703125,2G 1 1/41,12460 x 560 x 78965
OP 803906,5G 1 1/41,19580 x 590 x 89980
OP 904627,7G 1 1/41,44580 x 590 x 89980
OP 1005949,9G 2 1/21,87795 x 990 x 925160
OP 11072012,0G 2 1/21,94795 x 990 x 925165
OP 12083513,9G 2 1/22,34795 x 990 x 925170
OP 130120020,0G 33,79955 x 1220 x 1295303
OP 140144024,0G 34,29955 x 1220 x 1295303
OP 150180030,0G 35,29955 x 1220 x 1295345
OP 160210035,0G 35,89955 x 1220 x 1295345

Maximum pressure: 1.3MPa for OP 05 ÷ OP 90; 1.6MPa for OP 100 ÷ OP 130; 1.45MPa for OP 140 ÷ OP 160.

Feed voltage: 230V for OP 05 ÷ OP 110; 400V for OP 120 ÷ OP 160.

Coolant: R134a for OP 05 ÷ OP 30; R404a for OP 40÷OP 160.

Dew point +30C


 

 

Refrigerant dryers SGB and PGN series

TypeAir flowConnectionNominal power
kW
Dimensions
(L x W x H)
mm
Weight
kg
m3/hm3/min
SGB 002120,2G 3/80,16450 x 197 x 45518
SGB 004240,4G 3/80,17450 x 197 x 45518
SGB 006360,6G 3/80,20450 x 197 x 45520
SGB 009540,9G 1/20,24600 x 282 x 53032
SGB 012721,2G 1/20,33600 x 282 x 53033
SGB 0181081,8G 3/40,48700 x 352 x 60546
SGB 0241442,4G 3/40,63700 x 352 x 60555
SGB 0301803,0G 3/40,80700 x 352 x 60558
PGN 0402404,0G 1 1/20,58552 x 615 x 79165
PGN 0503005,0G 1 1/20,96552 x 615 x 79166
PGN 0603606,0G 1 1/20,95552 x 615 x 79168
PGN 0704207,0G 1 1/20,98552 x 615 x 79170
PGN 0804808,0G 1 1/21,23552 x 615 x 79173
PGN 11066011,0G 21,21672 x 920 x 1015140
PGN 14084014,0G 21,49672 x 920 x 1015144
PGN 180108018,0G 21,49672 x 920 x 1015150
PGN 220132022,0DN 802,111310 x 1010 x 1500400
PGN 270162027,0DN 802,761310 x 1010 x 1500420
PGN 370222037,0DN 803,191310 x 1010 x 1500450

Maximum pressure: 1.6MPa for SGB series; 1.2MPa for PGN series.

Feed voltage: 230V for SGB 002 ÷ PGN 080; 400V for PGN 110 ÷ PGN 370.

Coolant: R134a for SGB series; R407c for PGN series.

Dew point +30C


 

 